Troubleshooting by Indication on the Remote Controller
256
Remote Controller Display
U0
Applicable Models
VRVII and II-S Series
Method of Error Detection
Shortage of refrigerant is detected by discharge pipe
thermistor.
Error Decision Conditions
Micro-computer judge and detect if the system is
refrigerant shortage.
Error is not decided while the unit operation is
continued.
Supposed Causes
Shortage of gas or refrigerant system clogging
(incorrect piping)
Defective pressure sensor
Defective outdoor unit PCB
Defective thermistor