26 Centrifugal Chillers IM 1044-2
Insulating Motor Terminals
1. Insulate motor housing around terminals using thermal
foam.
2. Thermally insulate the motor terminals.
Use “SCOTCH” Sealant Tape on each end of terminal
on glass.
Install full length plus heat shrink tube (see picture to
right.)
Shrink with heat gun.
3. Install the flexible buss bars. (see picture at right) using a
backing wrench and tighten as shown below. The buss
bars are factory connected to the box main power
terminals and field connected to the motor terminals
Use Scotch® Linerless Rubber Splicing Tape to cover
the compressor terminal housing extending into the
terminal box. See Figure 14.
Top wrap with “SCOTCH” Sealant Tape starting at
base terminal and going out 2-in. onto the buss-bar.
Top wrap with "SCOTCH" 70 SELF-FUSING SILICONE RUBBER ELECTRICAL TAPE 70
starting at base terminal and going out 2-in.onto the buss-bar.
Top coat all this the 3M™ Scotchkote™ Electrical Coating 14853 (clear liquid)