10 Menu operation RC8CE202 © Danfoss 03/2013 AK-PC 781 Version 4.1x
Min. tm k tm value at minimum load.
Min. Reference °C Min. permissible condensing pressure reference
Max. Reference °C Max. permissible condensing pressure reference
Capacity Lim. night % Capacity limitation during night operation
Kp Amplication factor P/PI controller
Tn s Integration time for PI controller
VSD Min. speed % Minimum allowed speed before stop of Variable Speed drive (Low load condition)
VSD Start speed % Minimum speed for start of Variable speed drive (Must be set higher than
“VSD Min. Speed %”)
Pc max limit Bar Max. limit for condensing pressure
Pc max alarm delay m Time delay for "Pc max alarm"
Condenser fan status
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. ctrl. temp °C Actual temperature for control sensor (Po or S4)
Comp. ctrl. ref. °C Actual reference temp. for compressor capacity
(incl. external reference signal, if any)
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Compr. Cap % Reference for compressor capacity (deviations may be due to time delays)
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Ss Suction gas °C Actual suction gas temperature
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external contributions, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Pc Bar Condensing pressure (measured with the pressure transmitter)
Tc °C Condensing pressure in °C. (measured with the pressure transmitter)
Gc status Actual gas cooler operation:
0=O. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.
Pgc bar Actual gas cooler pressure
Pgc reference bar Actual reference for gas cooler pressure
Sd discharge gas °C Actual discharge gas temperature
Sgc °C Actual temperature at outlet from the gas cooler
Fan1/VSD status Status of the Fan 1
ON: Fan is running
OFF: Fan is not running
Fan2.... status As above for fan 2 to 8
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Heat recovery
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. ctrl. temp °C Actual temperature for control sensor (Po or S4)
Comp. ctrl. ref. °C Actual reference temp. for compressor capacity
(incl. external reference signal, if any)
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Compr. Cap % Reference for compressor capacity (deviations may be due to time delays)
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Ss Suction gas °C Actual suction gas temperature
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external contributions, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Pc Bar Condensing pressure (measured with the pressure transmitter)
Tc °C Condensing pressure in °C. (measured with the pressure transmitter)
Gc status Actual gas cooler operation:
0=O. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.