4 Menu operation RC8CE202 © Danfoss 03/2013 AK-PC 781 Version 4.1x
Main settings
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. ctrl. temp °C Actual temperature for control sensor (Po or S4)
Comp. ctrl. ref. °C Actual reference temp. for compressor capacity
(incl. external reference signal, if any)
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Compr. Cap % Reference for compressor capacity (deviations may be due to time delays)
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Ss Suction gas °C Actual suction gas temperature
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external contributions, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Pc Bar Condensing pressure (measured with the pressure transmitter)
Tc °C Condensing pressure in °C. (measured with the pressure transmitter)
Gc status Actual gas cooler operation:
0=O. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.
Pgc Bar Actual gas cooler pressure
Pgc reference bar Actual reference for gas cooler pressure
Sd discharge gas °C Actual discharge gas temperature
Sgc °C Actual temperature at outlet from the gas cooler
External Main Switch Status of input “Extern Main Switch. In pos. “OFF” the regulation is stopped by force
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Conguration lock Lock of conguration.
In order to select quick setup or select refrigerant type, the conguration lock must
be open. Note: ”Main switch must be OFF in order to set conguration lock in open
position
0: Open
1: Locked
Refrigerant type Po Select refrigerant type
0= not selected, 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1.
8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User dened 14=R32. 15=R227.
16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B.
23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A.
31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=XP10. 37=R407F.
Suction capacity control
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. ctrl. temp °C Actual temperature for control sensor (Po or S4)
Comp. ctrl. ref. °C Actual reference temp. for compressor capacity
(incl. external reference signal, if any)
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Compr. Cap % Reference for compressor capacity (deviations may be due to time delays)
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Ss Suction gas °C Actual suction gas temperature
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external contributions, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Pc Bar Condensing pressure (measured with the pressure transmitter)
Tc °C Condensing pressure in °C. (measured with the pressure transmitter)
Gc status Actual gas cooler operation:
0=O. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.
Pgc Bar Actual gas cooler pressure
Pgc reference Bar Actual reference for gas cooler pressure
Sd discharge gas °C Actual discharge gas temperature
Sgc °C Actual temperature at outlet from the gas cooler
MC dP0 oset K Actual displacement value for the suction pressure in connection with a “P0
Optimiser function (Master control function in AKA gateway)