EasyManua.ls Logo

Danfoss Ally - 7. Danfoss Ally Radiator Thermostat Technical Specifications

Danfoss Ally
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
AB440847594423en-000103 © Danfoss | FEC | 2023.12 |
Application Guide Heating Control Danfoss Ally™
Danfoss Icon™ E-error codes description
Alarm
code
Problem Solution
Er03 You have set-up a cooling applica-
tion that requires a reference room
thermostat to be appointed.
Please go to the thermostat in the desired ref-
erence room and enter the thermostat installer
menu. Set thermostat to ON in ME.6 “reference
room thermostat”.
Er05 Communication lost to Radio Mod-
ule.
Please check that the cable is properly connected
in the Radio Module and Danfoss Icon™ Master
Controller 24V.
Er06 Communication lost to room ther-
mostat.
Identify the room thermostat by looking at the
ashing outputs on the Danfoss Icon™ Master
Controller 24V, or look at the thermostats. Wake
up thermostat, then press
on the thermostat.
Faling thermostat will say “NET ERR”.
In some cases it is necessary to add a repeater
to establish a better wireless communication
between the Master Controller and Thermostat.
Replace batteries on room thermostat and per-
form a network test (activate NET TEST in menu
ME.3 on room thermostat).
Er07 Communication lost to Slave Con-
troller.
If wireless, check Radio Module connection tothe
Danfoss Icon™ Master Controller 24V. If wired
system, check the wire connecting the controllers.
Er08 Communication lost from Slave to
Master Controller.
If wireless, check Radio Module connection
toDanfoss Icon™ Master Controller 24V. If wired
system, check the wire connecting the controllers.
Er10 Communication lost to Repeater. Check that the repeater is plugged into outlet /
has not been removed and outlet is ON.
Er11 Communication lost to Expansion
Module.
Check that Expansion Module is slidded fully into
place.
Note! The Master controller must be turn o and on
again in order to register the expansion module.
Er12 Actuator defective.
The defective actuator output is
ashing.
Replace actuator.
Er14 Danfoss Icon™ Master Conroller can-
not be included as (become) a Slave
Controller because one or more room
thermostats, repeaters or Danfoss
Icon™ Master Controller 24V have
allready been included.
This Danfoss Icon™ Master Controller 24V has
to be factory reset to become Slave Controller.
(See description in chapter ”Reset or replace the
Danfoss Icon™ Master Controller”).

Other manuals for Danfoss Ally

Related product manuals