Basic principles Control of district heating circuits with or
without heat exchanger and for boiler-based
heating circuits
Typically,theowtemperatureisadjusted
accordingtothedesiredowtemperature.
• Adjustmentofowtemperature
Thedesiredowtemperatureiscalculated
in the ECL Comfort controller, based on the
outdoor temperature. The lower the outdoor
temperature,thehigherthedesiredow
temperature.
The motorized control valve is opened
graduallywhentheowtemperatureislower
thanthedesiredowtemperatureandvice
versa.
• Returntemperaturelimitation
The return temperature to the district heating
supply should not be too high. If so, the
desiredowtemperaturecanbeadjusted
(typically to a lower value) thus resulting in a
gradual closing of the motorized control valve.
In boiler-based heating supply the return
temperature should not be too low (same
adjustmentprocedureasabove).
• Roomtemperaturelimitation
If the measured room temperature does not
equal the desired room temperature, the
desiredowtemperaturecanbeadjusted.
• Circulationpumpcontrol
The circulation pump is ON when the desired
owtemperatureishigherthanauser-dened
value (factory setting: 20 °C ) or the outdoor
temperature is lower than a user-defined
value (factory setting: 2 °C).

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 110
CategoryController
LanguageEnglish

Related product manuals