EasyManua.ls Logo

Danfoss ECL Comfort 210 - Page 184

Danfoss ECL Comfort 210
199 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Situation2:
SLAVEcontroller:HowtoreactonaDHWtankheating/
chargingactivitysentfromtheMASTERcontroller
TheslavereceivesinformationaboutaDHWtankheating/
chargingactivityinthemastercontrollerandcanbesettoclose
theselectedheatingcircuit.
ECLcontrollerversions1.48(asfromAugust2013):
ThemasterreceivesinformationaboutDHWtankheating/
chargingactivityinthemastercontrolleritselfandalsoslavesin
thesystem.
ThisstatusisbroadcastedtoallECLcontrollersinthesystemand
eachheatingcircuitcanbesettoclosetheheating.
SLAVEcontroller:
Setthedesiredfunction:
Incircuit1/circuit2,goto‘Settings’>Application>’DHW
priority’:
DHWpriority(closedvalve/normal
operation)
11052
/12052
CircuitSettingrange
Choose
1/2OFF/ONOFF/ON
OFF:
Theflowtemperaturecontrolremainsunchangedduring
activeDHWheating/charginginthemaster/slave
system.
ON:
Thevalveintheheatingcircuitisclosedduringactive
DHWheating/charginginthemaster/slavesystem.
184|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort 210

Related product manuals