Situation3:
SLAVEcontroller:Howtomakeuseoftheoutdoortemperature
signalandsendinformationaboutthedesiredflow
temperaturebacktotheMASTERcontroller
Theslavecontrollerreceivesinformationaboutoutdoor
temperatureanddate/time.Themastercontrollerreceives
informationaboutthedesiredflowtemperaturefromslave
controllerswithanaddressfrom1...9:
SLAVEcontroller:
In
,gotoSystem>Communication>ECL485addr.
Changethefactorysetaddressfrom15toanaddress(1...9).
Eachslavemustbeconfiguredwithitsownaddress.
ECL485addr.(master/slaveaddress)
2048
CircuitSettingrange
Choose
0...151...9
Furthermore,eachslavecansendinformationaboutthedesired
flowtemperature(demand)ineachcircuitbacktothemaster
controller.
SLAVEcontroller:
Inthecircuitinquestion,gotoSettings>Application>Send
desiredT
ChooseONorOFF.
SenddesiredT
11500
/12500
CircuitSettingrange
Choose
1/2OFF/ONONorOFF
OFF:
Informationaboutthedesiredflowtemperatureisnot
senttothemastercontroller.
ON:
Informationaboutthedesiredflowtemperatureissent
tothemastercontroller.
IntheMASTERcontroller,theaddressin‘ECL485addr.(master/slave
address)’ ,IDno.2048,mustalwaysbe15.
VI.GU.L2.02
©Danfoss|2017.09|185
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort 210

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 210 and is the answer not in the manual?

Danfoss ECL Comfort 210 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 210
CategoryThermostat
LanguageEnglish

Related product manuals