ID
Parameter
NameA275.xA375.x
Setting
rangeFactoryUnitOwnsettings
11078PheatT1,2,31,2,3,4,55...4020°C
143
11085Priority1,2,31,2,3,4,5OFF;ONOFF
119
11093Frostpr.T1,2,31,2,3,4,55...4010°C
144
11141Ext.input1,2,3
OFF;S1;S2
;S3;S4;S5;
S6;S7;S8OFF
144
-||-1,2,3
OFF;S1;S2
;S3;S4;S5;
S6;S7;S8;
S9;S10OFF
-||-4,5
OFF;S1;S2
;S3;S4;S5;
S6;S7;S8;
S9;S10;S11;
S12;S13;S14
;S15;S16OFF
11142Ext.mode1,2,31,2,3
COMFORT;
SAVINGCOMFORT
145
-||-4,5
COMFORT
;SAVING;
FROSTPR.;
CONST.TCOMFORT
11177
Temp.min.
1,2,31,2,3,4,510...15010
°C
107
11178
Temp.max.
1,2,31,2,3,4,510...15090
°C
107
11179
Summer,
cut-out1,2,31,2,3,4,5OFF,1...5020°C
125
11182
Infl.-max.
1,2,31,2,3,4,5-9.9...0.0-4.0
113
11183
Infl.-min.
1,2,31,2,3,4,50.0...9.90.0
114
11184
Xp
4,5
5...250120
K
11185
Tn
4,5
1...99950
Sec
11186
Mrun
4,5
5...25060
Sec
11187
Nz
4,5
1...93
K
11189
Min.act.
time
4,5
2...5010
11364
Control,
delay
4,5
0...152
Min
133
11424
Min.offtime4,5
0...30
1Min
133
11500
Senddesired
T1,2,31,2,3,4,5
OFF;ONOFF
147
11607
LowX
4,5
10...15020
°C
11608HighX
4,5
10...150100°C
11609
LowY
1,2,310...15010
°C
-||-4,5
0.0...10.00.0
V
11610HighY1,2,310...150100°C
-||-4,5
0.0...10.010.0
V
12010ECAaddr.33,5OFF;A;BOFF
140
12011
Autosaving
33,5
OFF,-29...10-15°C
121
12012
Boost
33,5
OFF,1...99OFF
%
122