A375.1,exampleI
Upto8xboilerON/OFFcontrolforaheatingcircuit.Thefirsttwoboilers(highefficiency)havehighestpriority.
*=pressurereliefvalve
Thefirsttwoboilerscanbeheatpumps
TheextensionmoduleECA32isusedtocontrolboiler5,6,7and8.
Sequencefortheboilers:Boiler1,2,3-4-5-6-7-8.Nextday:Boiler1,2,4-5-6-7-8-3.Followingday:Boiler1,2,5-6-7-8-3
-4andsoon.
Burnerstepsareactivatedaccordingtoheatdemand.
Thelastburnerstepcanbedisablediftheoutdoortemperaureishigherthanasetvalue.
SpecialsettingsfortypeA375.1,examplei:
Navigation:
IDno.:
Recommendedsetting:
Heatingcircuit(circuit1)
Sequencetype(code)forcontrollingtheburners:
MENU\Settings\Boiler:'Sequencetype'
110722
Numberoftotalburnersteps:
MENU\Settings\Boiler:‘Steps'
110731....8
40|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375