MENU>Settings>Optimization
Totalstop
1x021
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
SeeAppendix“ParameterIDoverview
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced
accordingto:
desiredroomtemperatureinsavingmode
autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue
in‘Frostpr.Thecirculationpumpisstoppedbutfrost
protectionisstillactive,see'PfrostT'.
Totalstop=OFF
Totalstop=ON
X
=
Time
Y
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen
'Totalstop'isON.
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
1x026
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview
OFF:
Theoptimizedstoptimeisdisabled.
ON:
Theoptimizedstoptimeisenabled.
Example:OptimizationofComfortfrom07:00-22:00
X
=
Time
#1#
=
Schedule
#2#
=
Prestop=OFF
#3#
=
Prestop=ON
#4#
=
Optimizedstart
#5#
=
Optimizedstop
VI.GU.L2.02
©Danfoss|2017.09|125
OperatingGuideECLComfort210/296/310,applicationA275/A375