5.10Alarm
Alarmformonitoringtheflowtemperatureisonlyavailablein
circuit2inA275.3andA375.3applications.
ManyapplicationsintheECLComfort210and310serieshavean
alarmfunction.Thealarmfunctiontypicallyactivatesrelay4(ECL
Comfort210)orrelay6(ECLComfort310).
Thealarmrelaycanactivatealamp,ahorn,aninputtoanalarm
transmittingdeviceetc.
Therelayinquestionisactivatedaslongasthealarmcondition
ispresent.
Typicalalarms:
Actualflowtemperaturediffersfromthedesiredflow
temperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
5.10.1S9pressure
MENU>Settings>Alarm
LowX
1x607
Definitionofwhichvoltagevaluecorrespondstowhichpositionvalue.
Thevoltage(asa0-10voltsignal)comesfromapositionmeasuringin
M1andisappliedtoinputS11(ECA32).Thisinputvoltageisconvertedto
displaya%valueforthepositionofM1.
Seealso"Position"and"HighX" .
SeeAppendix“ParameterIDoverview
X
=
Volt
Y
=
Position
#1#
=
LowX
VI.GU.L2.02
©Danfoss|2017.09|149
OperatingGuideECLComfort210/296/310,applicationA275/A375