WhenECA30/31isinECAMENUmode,thedateandmeasured
roomtemperatureisdisplayed.
ECAMENU>ECAsettings>ECAsensor
RoomTOffset
Settingrange
Factorysetting
–10.0...10.0K0.0K
Themeasuredroomtemperaturecanbecorrected
withanumberofKelvin.Thecorrectedvalueisused
bytheheatingcircuitintheECLcontroller.
Minus
value:
Theindicatedroomtemperatureislower.
0.0K:
Nocorrectionofthemeasuredroomtemperature.
Plus
value:
Theindicatedroomtemperatureishigher.
Example:
RoomToffset:
0.0K
Displayedroomtemperature:
21.9°C
RoomToffset:
1.5K
Displayedroomtemperature:
23.4°C
ECAMENU>ECAsettings>ECAsensor
RHoffset(ECA31only)
Settingrange
Factorysetting
–10.0...10.0%0.0%
Themeasuredrelativehumiditycanbecorrected
withanumberof%-values.Thecorrectedvalueis
usedbytheapplicationintheECLcontroller.
Minus
value:
Theindicatedrelativehumidityislower.
0.0%:
Nocorrectionofthemeasuredrelativehumidity.
Plus
value:
Theindicatedrelativehumidityishigher.
Example:
RHoffset:
0.0%
Displayedrelativehumidity:
43.4%
RHoffset:
3.5%
Displayedrelativehumidity:
46.9%
ECAMENU>ECAsystem>ECAdisplay
Backlight(displaybrightness)
Settingrange
Factorysetting
0...10
5
Adjustthebrightnessofthedisplay.
0:
Weakbacklight.
10:
Strongbacklight.
174|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort 310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 310 and is the answer not in the manual?

Danfoss ECL Comfort 310 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 310
CategoryController
LanguageEnglish

Related product manuals