WhenECA30/31isinECAMENUmode,thedateandmeasured
roomtemperatureisdisplayed.
ECAMENU>ECAsettings>ECAsensor
RoomTOffset
Settingrange
Factorysetting
–10.0...10.0K0.0K
Themeasuredroomtemperaturecanbecorrected
withanumberofKelvin.Thecorrectedvalueisused
bytheheatingcircuitintheECLcontroller.
Minus
value:
Theindicatedroomtemperatureislower.
0.0K:
Nocorrectionofthemeasuredroomtemperature.
Plus
value:
Theindicatedroomtemperatureishigher.
Example:
RoomToffset:
0.0K
Displayedroomtemperature:
21.9°C
RoomToffset:
1.5K
Displayedroomtemperature:
23.4°C
ECAMENU>ECAsettings>ECAsensor
RHoffset(ECA31only)
Settingrange
Factorysetting
–10.0...10.0%0.0%
Themeasuredrelativehumiditycanbecorrected
withanumberof%-values.Thecorrectedvalueis
usedbytheapplicationintheECLcontroller.
Minus
value:
Theindicatedrelativehumidityislower.
0.0%:
Nocorrectionofthemeasuredrelativehumidity.
Plus
value:
Theindicatedrelativehumidityishigher.
Example:
RHoffset:
0.0%
Displayedrelativehumidity:
43.4%
RHoffset:
3.5%
Displayedrelativehumidity:
46.9%
ECAMENU>ECAsystem>ECAdisplay
Backlight(displaybrightness)
Settingrange
Factorysetting
0...10
5
Adjustthebrightnessofthedisplay.
0:
Weakbacklight.
10:
Strongbacklight.
174|©Danfoss|2017.09