Situation2:
SLAVEcontroller:HowtoreactonaDHWtankheating/
chargingactivitysentfromtheMASTERcontroller
TheslavereceivesinformationaboutaDHWtankheating/
chargingactivityinthemastercontrollerandcanbesettoclose
theselectedheatingcircuit.
ECLcontrollerversions1.48(asfromAugust2013):
ThemasterreceivesinformationaboutDHWtankheating/
chargingactivityinthemastercontrolleritselfandalsoslavesin
thesystem.
ThisstatusisbroadcastedtoallECLcontrollersinthesystemand
eachheatingcircuitcanbesettoclosetheheating.
SLAVEcontroller:
Setthedesiredfunction:
Incircuit1/circuit2,goto‘Settings’>Application>’DHW
priority’:
DHWpriority(closedvalve/normal
operation)
11052
/12052
CircuitSettingrange
Choose
1/2OFF/ONOFF/ON
OFF:
Theflowtemperaturecontrolremainsunchangedduring
activeDHWheating/charginginthemaster/slave
system.
ON:
Thevalveintheheatingcircuitisclosedduringactive
DHWheating/charginginthemaster/slavesystem.