EasyManuals Logo

Danfoss ECL Comfort A260 User Manual

Danfoss ECL Comfort A260
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #110 background imageLoading...
Page #110 background image
MENU>Settings>Tanktemperature
Stopdifference
1x194
OneDHWtanktemperaturesensor:
SetthenumberofdegreesaboveorbelowthedesiredDHWtemperature
thatwillstoptheDHWheating/charging.
TwoDHWtanktemperaturesensors:
SetthenumberofdegreesbelowthedesiredDHWtemperature,but
measuredbythelowertanktemperaturesensorthatwillstoptheDHW
heating/charging.
NOTE:Ifconditionforstop,relatedtothelowerDHWtanktemperature
sensor,ispresent,thestopisdonewhentheupperDHWtanktemperature
sensorhasatemperature2Khigherthanthestartdifferencelevel.
SeeAppendix“ParameterIDoverview
Value:
Setthenumberofdegrees.
OneDHWtanktemperaturesensor(examplewithpositive‘Stop
difference’value):
X
=
Time
#1#
=
Stopdifference(ID1x194)
#2#
=
DesiredDHWtemperature
#3#
=
ActualDHWtemperature
#4#
=
DHWheating/chargingactivity
OneDHWtanktemperaturesensor(examplewithnegative‘Stop
difference’value):
X
=
Time
#1#
=
Stopdifference(ID1x194)
#2#
=
DesiredDHWtemperature
#3#
=
ActualDHWtemperature
#4#
=
DHWheating/chargingactivity
110|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort A260

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort A260 and is the answer not in the manual?

Danfoss ECL Comfort A260 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort A260
CategoryController
LanguageEnglish

Related product manuals