EasyManuals Logo

Danfoss ECL Comfort A260 User Manual

Danfoss ECL Comfort A260
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #138 background imageLoading...
Page #138 background image
MENU>Settings>Controlparameters
Nz(neutralzone)
1x187
Whentheactualflow/ducttemperatureiswithintheneutralzone,the
controllerdoesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview
Settheacceptableflow/ducttemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh
variationinflowtemperature.
Theneutralzoneissymmetricalaroundthedesiredflow/duct
temperaturevalue,i.e.halfthevalueisaboveandhalfthevalueis
belowthistemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
1x189
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear
motor.
SeeAppendix“ParameterIDoverview
SettingexampleValuex20ms
240ms
10200ms
501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe
lifetimeoftheactuator(gearmotor).
138|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort A260

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort A260 and is the answer not in the manual?

Danfoss ECL Comfort A260 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort A260
CategoryController
LanguageEnglish

Related product manuals