6.8.8Sensoroffset(newfunctionalityasfromfirmware1.59)
Themeasuredtemperaturecanbeoffsetadjustedinorderto
compensateforcableresistanceoranot-optimumplaceforthe
temperaturesensor.Theadjustedtemperaturecanbeseenin"Raw
inputoverview"and"Inputoverview".
Commoncontroller>System>Sensoroffset
Sensor1...(temperaturesensor)
CircuitSettingrange
Factorysetting
**
Settingtheoffsetofthemeasuredtemperature.
Positive
offset
value:
Thetemperaturevalueisincreased
Negative
offset
value:
Thetemperaturevalueisdecreased
6.8.9Display
Backlight(displaybrightness)
60058
CircuitSettingrange
Factorysetting
0...10
5
Adjustthebrightnessofthedisplay.
0:
Weakbacklight.
10:
Strongbacklight.
Contrast(displaycontrast)
60059
CircuitSettingrange
Factorysetting
0...103
Adjustthecontrastofthedisplay.
0:
Lowcontrast.
10:
Highcontrast.
6.8.10Communication
Modbusaddr.
38
CircuitSettingrange
Factorysetting
1...247
1
SettheModbusaddressifthecontrollerispartofaModbus
network.
1...247:
AssigntheModbusaddresswithinthestatedsetting
range.
VI.GU.L2.02
©Danfoss|2017.09|169
OperatingGuideECLComfort210/296/310,applicationA275/A375