ID
Parameter
NameA275.xA375.x
Setting
rangeFactoryUnitOwnsettings
-||-5
OFF;S1;S2
;S3;S4;S5;
S6;S7;S8;
S9;S10;S11;
S12;S13;S14
;S15;S16OFF
12142Ext.mode2,32,3,5
COMFORT;
SAVINGCOMFORT
145
12147
Upper
difference33,5OFF,1...30OFFK
151
12148
Lower
difference33,5OFF,1...30OFFK
151
12149Delay33,51...9910Min
152
12150Lowesttemp.33,510...5030°C
152
12174Motorpr.33,5OFF,10...59OFFMin
136
12177Temp.min.33,510...15010°C
107
12178Temp.max.33,510...15045°C
107
12179
Summer,
cut-out33,5OFF,1...5020°C
125
12182
Infl.-max.
33,5-9.9...0.0-4.0
113
12183
Infl.-min.
33,50.0...9.90.0
114
12184
Xp
33,55...25080
K
12185
Tn
33,51...99930
Sec
12186
Mrun
33,55...25050
Sec
12187
Nz
33,51...93
K
12189
Min.act.
time
33,52...5010
12193
Charge
difference221...50
15
K
109
12194
Stop
difference22-50...503K
109
12195
Start
difference22-50...-1-3K
111
12500
Senddesired
T
2,32,3,5
OFF;ONON
147
13041
DHWP
post-run
31,3,50...300Min
141
13051
Ch.-o.valve/
P31,3,5
OFF;ONON
142
13053
Tank,sec./
prim.31,3,5
OFF;ONOFF
142
13093
Frostpr.T
33,55...4010
°C
144
13122
Day:
33,50...1270
13123
Starttime
33,50...470
13124
Duration
33,510...600120
Min
13125DesiredT33,5OFF,10...110OFF°C
196|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375