ApplicationA375.1(upto4burnersteps)
Terminal
Description
Max.load
19
PhaseforalarmandburnerB4
18
Alarm(A1)
4(2)A/230Va.c.*
17
B4
BurnerON/OFF4(2)A/230Va.c.*
16
PhaseforburnerB3
15
B3
BurnerON/OFF4(2)A/230Va.c.*
14
Phaseforpumpandburners
13
B2
BurnerON/OFF4(2)A/230Va.c.*
12
B1
BurnerON/OFF4(2)A/230Va.c.*
11
P1
CirculationpumpON/OFF
4(2)A/230Va.c.*
10
Supplyvoltage230Va.c.-neutral(N)
9
Supplyvoltage230Va.c.-live(L)
*Relaycontacts:4Aforohmicload,2Aforinductiveload
Factoryestablishedjumpers:
5to8,9to14,Lto5andLto9,Nto10
VI.GU.L2.02
©Danfoss|2017.09|53
OperatingGuideECLComfort210/296/310,applicationA275/A375