MENU>Settings>Tanktemperature
Stopdifference
1x194
OneDHWtanktemperaturesensor:
SetthenumberofdegreesaboveorbelowthedesiredDHWtemperature
thatwillstoptheDHWheating/charging.
TwoDHWtanktemperaturesensors:
SetthenumberofdegreesbelowthedesiredDHWtemperature,but
measuredbythelowertanktemperaturesensorthatwillstoptheDHW
heating/charging.
NOTE:Ifconditionforstop,relatedtothelowerDHWtanktemperature
sensor,ispresent,thestopisdonewhentheupperDHWtanktemperature
sensorhasatemperature2Khigherthanthestartdifferencelevel.
SeeAppendix“ParameterIDoverview
Value:
Setthenumberofdegrees.
OneDHWtanktemperaturesensor(examplewithpositive‘Stop
difference’value):
X
=
Time
#1#
=
Stopdifference(ID1x194)
#2#
=
DesiredDHWtemperature
#3#
=
ActualDHWtemperature
#4#
=
DHWheating/chargingactivity
OneDHWtanktemperaturesensor(examplewithnegative‘Stop
difference’value):
X
=
Time
#1#
=
Stopdifference(ID1x194)
#2#
=
DesiredDHWtemperature
#3#
=
ActualDHWtemperature
#4#
=
DHWheating/chargingactivity
110|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort A315

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort A315 and is the answer not in the manual?

Danfoss ECL Comfort A315 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort A315
CategoryController
LanguageEnglish

Related product manuals