ApplicationA375.2upto2burnersteps,P4isthecirculationpumpintheDHWcircuit
ApplicationA375.3upto2burnersteps,P4isthecirculationpumpinheatingcircuit2
Terminal
Description
Max.load
19
PhaseforalarmandburnerB2
18
Alarm(A1)
4(2)A/230Va.c.*
17
B2
BurnerON/OFF4(2)A/230Va.c.*
16
PhaseforpumpP4
15
P4
Circulationpump
4(2)A/230Va.c.*
14
Phaseforpumpsandburner
13
P3
DHWheatingpump,circuit2(A375.2)orcircuit3(A375.3)
4(2)A/230Va.c.*
12
B1
BurnerON/OFF4(2)A/230Va.c.*
11
P1
CirculationpumpON/OFF,circuit1
4(2)A/230Va.c.*
10
Supplyvoltage230Va.c.-neutral(N)
9
Supplyvoltage230Va.c.-live(L)
8
PhaseformotorizedchangeovervalveoutputM1
7
M1
Motorizedchangeovervalve,DHWcircuitdirection,circuit2(A375.2)orcircuit3(A375.3)
0.2A/230Va.c.
6
M1
Motorizedchangeovervalve,heatingcircuitdirection,circuit2(A375.2)orcircuit3(A375.3)
0.2A/230Va.c.
5
PhaseformotorizedcontrolvalveM2,circuit2
4
M2
Motorizedcontrolvalve-opening,circuit2(A375.3)
0.2A/230Va.c.
3
M2
Motorizedcontrolvalve-closing,circuit2(A375.3)
0.2A/230Va.c.
*Relaycontacts:4Aforohmicload,2Aforinductiveload
Factoryestablishedjumpers:
5to8,9to14,Lto5andLto9,Nto10
VI.GU.L2.02
©Danfoss|2017.09|55
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort A315

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort A315 and is the answer not in the manual?

Danfoss ECL Comfort A315 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort A315
CategoryController
LanguageEnglish

Related product manuals