EasyManuals Logo

Danfoss ECL Comfort A368 Service Guide

Danfoss ECL Comfort A368
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
© Danfoss | 2017.06 | 9
VI.LV.H1.02
Service guide ECL 296 / ECL 310 Modbus
7.3 Individual houses (without repeater)
1) = surge protector
As there is no repeater used in this node, there is no isolated channels created. S.Gnd is not connected to earth (PE).
Input cable (coming from central heating station) shield MUST be oating and output cable shield is connected to earth. Or the input and
output shield continuity is maintained and it is not connected to earth (As shown above).
This is to maintain single point earthing in each network, on common reference signal (S.Gnd) and shield cable (Refer section 5 point 5,
6).

Other manuals for Danfoss ECL Comfort A368

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort A368 and is the answer not in the manual?

Danfoss ECL Comfort A368 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort A368
CategoryController
LanguageEnglish

Related product manuals