InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Settings>Application
MENU>Settings>Controlpar.2
1.steplevel
1x368
CircuitSettingrange
Factorysetting
All
**
ThetotalcontrolrangeiscoveredbyM2withintheset%value.
MENU>Settings>Application
MENU>Settings>Controlpar.2
2.steplevel
1x369
CircuitSettingrange
Factorysetting
All
**
Fromtheset%valueandupto100%,thecontroliscoveredbyM1.
MENU>Settings>Controlpar.,fan
MENU>Settings>Controlpar.,inlet
MENU>Settings>Controlpar.,outlet
X1
1x406
CircuitSettingrange
Factorysetting
All
**
Denitionofwhichvoltagevaluecorrespondstowhichpressurevalue.
Thevoltage(asa0-10voltsignal)comesfromapressuretransmitterandis
appliedtotherelevantinput.
Thisinputvoltageisconvertedtodisplayapressurevalue(inPascal).
Seealso"Pressure"and"X2".
X
=
Volt
Y
=
Pressure
#1#
=
'X1'