InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Settings>Controlpar.,fan
MENU>Settings>Controlpar.,inlet
MENU>Settings>Controlpar.,outlet
X2
1x407
CircuitSettingrange
Factorysetting
All
**
Denitionofwhichvoltagevaluecorrespondstowhichpressurevalue.
Thevoltage(asa0-10voltsignal)comesfromapressuretransmitterandis
appliedtotherelevantinput.
Thisinputvoltageisconvertedtodisplayapressurevalue(inPascal).
Seealso"Pressure"and"X1".
X
=
Volt
Y
=
Pressure
#1#
=
'X2'
MENU>Settings>Controlpar.,inlet
MENU>Settings>Controlpar.,outlet
Pressure
CircuitSettingrange
Factorysetting
All
**
Theactualpressure,measuredinPascal.
A0-10voltsignalcomesfromapressuretransmitterandisappliedto
relatedinput.
Thisinputvoltageisconvertedtothedisplayedpressurevalue.
Accesstoconversion(scale)settings:Pushdial.