EasyManua.ls Logo

Danfoss ECL Comfort A368

Danfoss ECL Comfort A368
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Application
Mexercise(valveexercise)
1x023
CircuitSettingrange
Factorysetting
All
**
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.

OFF:

ON:


MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
1x052
CircuitSettingrange
Factorysetting
All
**
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen
DHWheating/chargingisactiveinthemaster.

OFF:



ON:


*Thedesiredowtemperatureissettothevaluesetin
‘Frostpr.T’

MENU>Settings>Application
MENU>Settings>Fan/acc.control
PfrostT(circulationpump,frostprotectiontemp.)
1x077
CircuitSettingrange
Factorysetting
All
**
Frostprotection,basedontheoutdoortemperature.
Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P
frostT ,thecontrollerautomaticallyswitchesONthecirculationpump(for
exampleP1orX3)toprotectthesystem.

OFF:

Value:











Related product manuals