OperatingGuideECLComfort310,applicationA368
MENU>Settings>Application
Mexercise(valveexercise)
1x023
CircuitSettingrange
Factorysetting
All
**
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.

OFF:

ON:


MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
1x052
CircuitSettingrange
Factorysetting
All
**
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen
DHWheating/chargingisactiveinthemaster.

OFF:



ON:


*Thedesiredowtemperatureissettothevaluesetin
‘Frostpr.T’

MENU>Settings>Application
MENU>Settings>Fan/acc.control
PfrostT(circulationpump,frostprotectiontemp.)
1x077
CircuitSettingrange
Factorysetting
All
**
Frostprotection,basedontheoutdoortemperature.
Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P
frostT ,thecontrollerautomaticallyswitchesONthecirculationpump(for
exampleP1orX3)toprotectthesystem.

OFF:

Value:









