MENU>Settings>Application
PheatT(heatdemand)
1x078
Whenthedesiredflowtemperatureisabovethesettemperaturein‘PheatT’ ,
thecontrollerautomaticallyswitchesONthecirculationpump.
SeeAppendix“ParameterIDoverview”
Value:ThecirculationpumpisswitchedONwhenthedesired
flowtemperatureisabovethesetvalue.
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
MENU>Settings>Application
Frostpr.T(frostprotectiontemp.)
1x093
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe
systemagainstfrost(atheatingcut-out,totalstopetc.).
WhenthetemperatureatS3getslowerthanthesetting,themotorized
controlvalveopensgradually.
SeeAppendix“ParameterIDoverview”
Thefrostprotectiontemperaturecanalsobesetinyourfavorite
displaywhenthemodeselectorisinfrostprotectionmode.
144|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375