MENU>Settings>Alarm
HighX
1x608
Definitionofwhichvoltagevaluecorrespondstowhichpositionvalue.
Thevoltage(asa0-10voltsignal)comesfromapositionmeasuringin
M1andisappliedtoinputS11(ECA32).Thisinputvoltageisconvertedto
displaya%valueforthepositionofM1.
Seealso"Position"and"LowX".
SeeAppendix“ParameterIDoverview”
X
=
Volt
Y
=
Position
#1#
=
HighX
MENU>Settings>Alarm
Alarmhigh
1x614
Whenthemeasuredvaluegetshigherthanthesetvalue,thealarmwill
beactivated.
SeeAppendix“ParameterIDoverview”
Value:Setthealarmvalue
MENU>Settings>Alarm
Alarmlow
1x615
Whenthemeasuredvaluegetslowerthanthesetvalue,thealarmwillbe
activated.
SeeAppendix“ParameterIDoverview”
Value:Setthealarmvalue
MENU>Settings>Alarm
Alarmtime-out
1x617
Thealarmisactivatedwhenthealarmreasonhasbeenpresentforalonger
time(inseconds)thanthesetvalue.
SeeAppendix“ParameterIDoverview”
Value:Setthealarmtime-out
150|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375