A375.1,examplee
Twoboilerswith2xburnerON/OFFcontrolforaheatingcircuit.
*=pressurereliefvalve
Fixedsequenceforeachboiler:Burner1(3)mustbeswitchedONbeforeburner2(4)canbeswitchedON.
Rotatingsequencefortheboilers:Boiler1isactivebeforeboiler2.Nextdayboiler2isactivebeforeboiler1.
Burnerstepsareactivatedaccordingtoheatdemand.
Thelastburnerstepcanbedisablediftheoutdoortemperaureishigherthanasetvalue.
SpecialsettingsfortypeA375.1,examplee:
Navigation:
IDno.:
Recommendedsetting:
Heatingcircuit(circuit1)
Sequencetype(code)forcontrollingtheburners:
MENU\Settings\Boiler:'Sequencetype'
11072
4
Numberoftotalburnersteps:
MENU\Settings\Boiler:‘Steps'
11073
4
36|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375