OperatingGuideECLComfort310,applicationA368
MENU>Settings>Boiler
MENU>Settings>Controlpar.
MENU>Settings>Controlpar.,cool.
MENU>Settings>Controlpar.,fan
MENU>Settings>Controlpar.,inlet
MENU>Settings>Controlpar.,outlet
MENU>Settings>Controlpar.1
MENU>Settings>Controlpar.2
MENU>Settings>Controlpar.3
MENU>Settings>Controlpar.,Pcirc.
MENU>Settings>Controlpar.,Prell
Xp(proportionalband)
1x184
CircuitSettingrange
Factorysetting
All
**
MENU>Settings>Boiler
MENU>Settings>Controlpar.
MENU>Settings>Controlpar.,cool.
MENU>Settings>Controlpar.,fan
MENU>Settings>Controlpar.,inlet
MENU>Settings>Controlpar.,outlet
MENU>Settings>Controlpar.1
MENU>Settings>Controlpar.2
MENU>Settings>Controlpar.3
MENU>Settings>Controlpar.,Pcirc.
MENU>Settings>Controlpar.,Prell
Tn(integrationtimeconstant)
1x185
CircuitSettingrange
Factorysetting
All
**
MENU>Settings>Boiler
MENU>Settings>Controlpar.
MENU>Settings>Controlpar.,cool.
MENU>Settings>Controlpar.1
MENU>Settings>Controlpar.2
Mrun(runningtimeofthemotorizedcontrolvalve)
1x186
CircuitSettingrange
Factorysetting
All
**
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove
fromfullyclosedtofullyopenposition.
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Seatedvalves
Example:
5.0mmx15sec./mm=75sec.
Rotatingvalves
Example:90degr.x2sec./degr.=180sec.