N021 SH reference mode 3027 2 0 = Fixed SH | 1 = Loadap | 2 = MSS | 3 = Delta temp
N107 SH xed setpoint ( K) 3028 7 Range 2 K – 40 K
N009 SH max. ( K) 3029 9 Range 4 K – 40 K
N010 SH min. ( K) 3030 4 Range 2 K – 9 K
N116 SH ref. delta temp. factor ( %) 3035 65 Range 20 – 100
For a detailed parameter list and explanation, please check the EKE data sheet.