© Danfoss | DCS (MWA) | 2016.12
DKRCI.PI.HS1.A6.ML | 520H6354 | 4
ENGLISH
Installation
Refrigerants
Applicable to HCFC, HFC, R717(Ammonia) 
and R744 (CO
2
).
Flammable hydrocarbons are not
recommended. 
The valve is only recommended for use in 
closed circuits. For further information please 
contact Danfoss.
Please note: 
The ICLX function modules can only 
be used in housings 
produced in or after week 49 2012; 
thus the week code on the housing 
must be 4912 or higher.
Temperature range
–60/+120°C (–76/+248°F)
Pressure
The valves are designed for a max.
working pressure of 52 bar g (754 psi g).
Application
The ICLX is used in suction lines for the 
opening against high dierential pressure, 
e.g. after hot gas defrost in large industrial 
refrigeration systems with ammonia, 
ourinated refrigerants or CO
2
.
The ICLX opens in two steps: 
Step one opens to approx. 10% of the 
capacity, when the pilot solenoid valves are 
activated.
Step two opens automatically after the 
pressure dierential across the valve reaches 
approximately 1 bar.
External pressure
The external pressure applied to the ICLX 
should always be 1.5 bar higher than the inlet 
pressure of the valve. This will give the valve a 
MOPD of 28 bar. If the external pressure is  
2 bar higher than the inlet pressure the MOPD 
of the ICLX will be 40 bar.
Electrical wiring
The ICLX valve is a normally closed design. 
To ensure that the valve operates as normally 
closed it is important that the EVM NC pilot is 
mounted in the pilot port next to the external 
pressure inlet (g. 2). For normal operation 
mode both pilots should be energized 
simultaneously, e.g. same signal can be used 
for both pilots.
Coil requirements
Both coils must be IP67.
EVM NC:  10W ac (or higher) for MOPD  
  up to 21 bar
EVM NC:  20W ac for MOPD 21 → 40 bar
EVM NO:  10W ac (or higher)
The valve will have a malfunction 
in systems where the pressure 
dierential across the valve in normal 
open conditions will exceed 1 bar (15 
psig). In this case the step two of the 
valve will close.
Orientation
The valve must be installed with the arrow in 
the direction of the ow and with the pilots 
pointing in one of the directions shown in 
g.1. Downwards pointing pilots (any angle) 
is not possible. The top cover can be rotated 4 
X 90° in relation to the valve body. 
If the ICLX is installed with a vertical pilot 
orientation (see g. 1) attention should be 
paid to have the EVM NO in lower position. If 
needed rotate the top cover.
The valve is tted with a spindle for manual 
opening. Make sure that the external pilot 
line is connected to the upper side of the 
main line so that any dirt and oil from the 
plant will not nd its way into the pilot line.
The valve is designed to withstand a high 
internal pressure. However, the piping system 
should be designed to avoid liquid traps and 
reduce the risk of hydraulic pressure caused 
by thermal expansion. It must be ensured 
that the valve is protected from pressure 
transients like “liquid hammer” in the system.
Welding (g. 5 and 8a)
The top cover (g. 8a, pos. 2) and function 
module (g. 8a, pos. 3), must be removed 
before welding to prevent damage to o-rings 
and teon (PTFE) in the function module. 
Often the cover and function module can be 
removed while still assembled (g. 3a), but if 
the internal O-rings stick to the metal surface 
it is necessary to disassemble in 2 steps  
(g. 3b). In both cases the parts can be lifted 
out by the careful use of 2 screwdrivers.
Note:  Remove all parts from the valve body 
before welding (as shown in g. 5). 
The internal surfaces and weld   
connections of the enclosed ICLX 
valve have been applied with    
an anti-corrosion treatment.
In order to maintain the eectiveness 
of this anti-corrosion treatment, it is 
important to ensure that the valve is 
disassembled just prior to the welding 
process being undertaken.
In the event that the function modules are 
to be left disassembled for even a short 
period, please ensure that the function 
modules are  further protected by placing 
in a polyethylene bag or by applying a rust 
protection agent (e.g. refrigeration oil or 
BRANOROL) on the surfaces.
Only materials and welding methods, 
compatible with the valve body material, 
must be applied to the valve body. 
Avoid welding debris and dirt in the
valve body and the function module. The 
valve body must be free from stresses 
(external loads) after installation.
The valves must not be mounted in systems 
where the outlet side of the valve is open 
to atmosphere. The outlet side of the valve 
must always be connected to the system 
or properly capped o, for example with a 
welded-on end plate.
Assembly
Remove welding debris and any dirt from 
pipes and valve body before assembly. Check 
that the o-rings are intact before replacing 
the function module. If possible, apply some 
refrigeration oil to ease the insertion and to 
protect the o-rings.  Check that the top gasket 
has not been damaged. If the surface has 
been damaged or the gasket has been bent, it 
must be replaced.
Tightening (g. 6)
Tighten the top cover with a torque wrench, 
to the values indicated in the table.
Colours and identication
The ICLX valves are Zinc-Chromated from 
factory. The Zinc-Chromatization does not 
cover the welding connections.
If further corrosion protection is required, the 
valves can be painted.
The external surface of the valve housing 
must be protected against corrosion with 
a suitable top coating after installation 
involving welding and consequent assembly.
Protection of the ID plate when painting the 
valve is recommended.
  Important note for ICLX valves:
  The ICLX valve is kept in its open  
  position by hot gas. The hot gas  
  condenses in the cold valve and  
  creates liquid under the servo piston. 
When the pilot valves change status to close 
the ICLX, the pressure on the servo piston 
equalises with the suction pressure through 
the pilot valve.
This equalisation takes time because 
condensed liquid is present in the valve.
The exact time taken from when the pilot 
valves change position to complete closing 
of the ICLX will depend on temperature, 
pressure, refrigerant and size of valve. Thus 
an exact closing time for the valves cannot 
be given but, in general, lower temperatures 
give longer closing times.
It is very important to take the closing times 
into consideration when hot gas defrost is 
performed on evaporators.
Steps must be taken to ensure that the 
hot gas supply valve is not opened before 
the ICLX in the suction line is completely 
closed. If the hot gas supply valve is opened 
before the ICLX in the suction line is closed, 
considerable energy will be lost and 
potentially dangerous situations might arise 
because of “liquid hammer”. In ICLX valves, 
the spring-loaded second stage might be 
induced to hammer by gas and liquid being 
forced through the valve at Δp > 1.5 bar 
across the ICLX. The nal result could be 
severe damage to the valve.
As a rule of thumb a closing time of 2 
minutes can be used as a starting point.
The optimum closing time for each 
individual system must be determined 
at initial start-up of the plant at intended 
operational conditions. It is recommended 
to check if the closing time needs to be 
changed when conditions changes (suction 
pressure, ambient temp. etc.) and closing 
time should be checked at service of the 
valve.
Once the optimum closing time has been
identied it is recommended to add a safety
margin of 30 sec. to the optimum closing 
time.
Maintenance
Service
The ICLX valves can be disassembled for 
service purposes. 
Only skilled and trained refrigeration 
engineers are allowed to service the ICLX 
valves.
Do not open the valve while the valve is still 
under pressure.
Pressure relief can be done by carefully 
opening the manual operating spindle. Small 
grooves along the thread will release 
refrigerant into open air. This operation must 
only be done after providing the correct 
countermeasures under local legislation.