19
VLT is a registered Danfoss trade mark MG.10.P2.22
Memory
Mapping
(continued)
VLT 6000 Register Maps (65536 registers total)
Address (Decimal) Description
00001 IND (index word)
00002 Modbus Communications Timeout Value (10 millisecond units)
00003 Drive Communications Timeout Value (10 millisecond units)
00004 – 00009 Reserved
00010
Parameter 001, Language
↓ ↓
00170
Parameter 017, Operating State at Power-up
00180 – 09999 Reserved
01000
Parameter 100, Configuration
↓ ↓
01170
Parameter 117, Motor Thermal Protection
01180 – 01999 Reserved
02000
Parameter 200, Output Frequency Range
↓ ↓
02280
Parameter 228, Warning: High Feedback
02290 – 02999 Reserved
03000
Parameter 300, Terminal 16 Digital Input
↓ ↓
03280
Parameter 328, Pulse Feedback, Max. Freq.
03290 – 03999 Reserved
04000
Parameter 400, Reset Function
↓ ↓
04270
Parameter 427, PID Lowpass Filter Time
04280 – 04999 Reserved
05000
Parameter 500, Protocol
↓ ↓
05660
Parameter 566, FLN Time Function
05670 – 05999 Reserved
06000
Parameter 600, Operating Data: Operating Hours
↓ ↓
06310
Parameter 631, Nameplate: Communication Option Ordering No.
06320 – 06999 Reserved
07000
Parameter 700, Relay 6, Output Function
↓ ↓
07110
Parameter 711, Relay 9, Off Delay
07120 – 65536 Reserved