EXAMPLE ONE: Start Motor, Run Speed 40%
All values are in hexadecimal.
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Slave
Addres
Function Coil Addr HI Coil Addr LO # of Coils HI # of Coils LO Byte Count Force Data HI
Coils (0-7)
01 0F 00 00 00 20 04 7C
Byte 8 Byte 9 Byte 10 Byte 11
Force Data
LO
Coils (8-15)
Force Data HI
Coils (1 -23)
Force Data
LO
Coils (2 -31)
Error Check
04 99 19 [37] [43]
Message rMessage r
Message rMessage r
Message r
eturetur
eturetur
etur
ned to Modbus master frned to Modbus master fr
ned to Modbus master frned to Modbus master fr
ned to Modbus master fr
om Modbus Rom Modbus R
om Modbus Rom Modbus R
om Modbus R
TU option carTU option car
TU option carTU option car
TU option car
dd
dd
d
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6
Slave
Address
Function Coil Addr HI Coil Addr LO No. of Coils
HI
No. of Coils
LO
Error Check
01 0F 00 00 00 20 [54] [13]
Modbus function 0F
HEX
(Force Multiple Coils).
Message sent to Modbus RTU option card from Modbus masterMessage sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus masterMessage sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Drive Start Command, with bytes reversed (see FC Protocol Control Word Bit Descriptions):
binary (bit 15 through bit 00) 0000010001111100 = 047C
Modbus message string:
[01] [0F] [00] [00] [00] [20] [04] [7C] [04] [99] [19] [37] [43]
{
Start Command: 0000010001111100 = 047C
HEX
(reversed)
(see FC Protocol Control Word Bit Descriptions)
Modbus message string:
[01] [0F] [00] [00] [00] [20] [04] [7C] [04] [99] [19] [37] [43]
{
NOTE: Speed Command: 4000
HEX
= 100% speed
40% of 4000
HEX
= 1999
HEX
(reversed)