EasyManua.ls Logo

Danfoss OPTYMA Plus Series - Factory Reset Procedure; Controller Replacement

Danfoss OPTYMA Plus Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 BC08728642552802-001001
Manual
Controller Installation
• Turn OFF the main power switch
• Remove the new controller (remove all plugs, 2 x I-type screws and controller)
• Install the new controller
• Turn ON main power switch again, no factory reset needed
• After a short time message “typ” appears on the screen
• Follow same steps as shown in preceding chapter fifth row and following
spare part code controller SINGLE pack: 118U3465
Controller Replacement of a
unit on site
• The setpoint condensing temperature is calculated from the measured ambient temperature plus an
adjustable Temperature Offset (called Reference) and controlled by the fan speed
• Factory setting of Reference = 8.0K
• The Reference is accessible by pressing short the middle button of the controller
• When Reference is shown, it can be modified with the upper or lower button
• Additionally to this the control of the condensing temperature can be limited by following
parameters:
“r82” = minimal condensing temperature (factory set: 10.0°C)
“r83” = maximal condensing temperature (factory set: 40.0°C)
Control of condensing pressure
Control
• The controller optimizes the regulation of the crankcase heater itself. The heating power depends on
the ambient temperature and suction pressure and is controlled by Pulse Width modulation
• There is no change of parameters “P45”, “P46” and “P47” necessary on site
• The fan speed is controlled by PI-control, depends on the actual value and the setpoint of the
condensing temperature
• There is no change of parameters “F14” and “F21” to be provided on site
Control of crankcase heater
Control of Fan Speed
• Turn OFF the main power switch
• While holding simultaneously the up and down button, turn ON the main switch
• Message FAC is displayed, means “FACTORY RESET” restores factory settings
• After a short time message “typ” appears on the screen
• Activate parameter menu and go to parameter o61 (unit type)
• Enter the value 1 to 57 depending on the type of condensing unit (see table 1 on page 3)
• Store the entered value by pressing the middle button of the controller
• After 15 seconds without action the message “ref” appears on the screen
• Activate parameter menu and go to parameter o30 (refrigerant)
• Change the value to 3 (for refrigerant R134a),17(R507), 20(R407C), 19(R404A), 21(R407A), 37(R407F),
40(R448A), 41(R449A), 42(R452A) or 13 (R513A)
For INVERTER units only:
- Set parameter c71 to 2 (variable speed compressor)
- Set parameter o37 to 7 (frequency converter alarm on DI2)
• Store the entered value by pressing the middle button of the controller
• Go to parameter o67 (store values as factory setting)
• Change the value to “on”
• Validate the parameter entered by pressing the middle button of the controller
• After 15 seconds without action the message “OFF” appears on the screen
• Activate parameter menu and go to parameter r12 (main switch)
• Change the value to 1 (condensing unit will start if cooling demand from cold room controller)
• The “Day / Night” function must be reprogrammed too (see chapter Commissioning - Day/Night
- Function)
Factory reset
(all factory parameters can be
restored by the following
procedure)

Table of Contents