13BC08728642552802-001001
Manual
Controller Installation
Safety Parameter “Low
Pressure” for R448A / R449A /
R452A
Safety Parameter “High
Pressure” for R448A / R449A /
R452A
0
Dierential: Parameter c76
Scroll and Recip: 0,7bar
Low pressure switch: Cut-Out
Scroll and Recip: -0,3bar
Min. suction pres.: Param. c75
INVERTER: 2,0bar
Scroll: 1,5bar Recip: 0,3bar
Low pressure switch: Cut-In
Scroll and Recip: 0,5bar
Suction Pressure
“Electronic“ Safety - LP
“Mechanical“ Safety - LP
High pressure switch: Cut-In
Scroll and Recip: 24bar
0
Max. Pressure: Parameter c73
Scroll + "blue" Recip.: 28bar
"black" Recip.: 23bar
Dierential: Parameter c74
Scroll and Recip: 3,0bar
High pressure switch: Cut-Out
Scroll and Recip: 31bar
Discharge Pressure
“Electronic“ Safety - LP
“Mechanical“ Safety - HP