Product description
2.3 Condensing unit
nomenclature system
2.4 Label
OP - M P L M 028 VVL P01 E
1 2 3 4 5 6 7 8
1 Application M = MBP
2 Design P = Packaged units
3 Refrigerant
L = R404A, R407A, R407F
P= R404A, R407A, R407F, R448A, R449A
4 Condenser type
M = Standard with micro channel heat exchanger
Tambient max 43 deg C
5 Displacement 028 = 28 cm
3
/rev
6 Compressor platform VVL = variable speed scroll VLZ compressor
7 Version P01
8 Electrical code E = Compressor 400 V/3 phase/50 Hz, fan 230 V/1 phase/ 50 Hz
OP-MPPM044VVLP01E
Code Number.: 114X4334
Application MBP IP 54
Refrigerant (1) R448A/R449A/R407F
M.W.P HP (1) 28 bar (2)
LP (1) 7 bar (2)
Voltage 380V-400V~3N~50Hz
LRA Inverter Driven MCC 12.1 A
Serial No. 123456CG1015
MADE IN INDIA
A
B
C
D
E
F
G
H
R407A/R404A (2)
A: Model
B: Code number
C: Application
D: Refrigerant
E: Housing Service Pressure
F: Supply voltage, M§aximum Current Consumption
G: Serial Number and bar code
H: Protection
Serial-no.: XXXXXXCGWWYY
XXXXXX = ascending number
CG = manufacturing plant
WW = week of production
YY = year of production
7FRCC.PC.044.A6.02
Application Guidelines