EasyManua.ls Logo

Danfoss Optyma Plus - Display, Input, and Sensor Configuration; Display Signal Selection and Pressure Transmitter Ranges; Refrigerant Type and Digital Input D2 Functions; Condensing Unit Type and S3 Sensor Configuration

Danfoss Optyma Plus
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2018
EcoDesign
For more information related to EcoDesign compliance, please refer to Coolselector®
coolselector.danfoss.com or contact Danfoss
Product description
2.8 Cooling capacities, sound data, power consumption
Optyma
Plus INVERTER, R407A
Model number
Code
number
Compressor
Compressor
speed, rps
Tamb [°C]
Cooling capacity Q [kW] P [kW] EcoDesign (2)
Sound power
level dB(A)
Sound pressure
level 10 m dB(A)
Te [°C]
COP
(1)
Q [kW] P [kW] COP
A
SEPR
-15 C -10 C -5 C 0 C 5 C -10°C
OP-MPPM028VVLP01E 114X4302 VLZ028TGA
30
27 1435 1797 2227 2732 3320
72.8 41.8
32 1345 1686 2092 2570 3128 899 1.88
38 - 1557 1934 2380 2902
43 - - - - -
50
27 2382 2994 3711 4543 5499
73.4 42.4
32 2243 2829 3515 4310 5224 1333 2.12
38 - 2622 3267 4015 4876
43 - 2442 3050 3757 4571
75
27 3499 4412 5470 6686 8069
74.0 43.0
32 3306 4177 5183 6339 7654 2005 2.08
38 - 3879 4821 5901 7131
43 - 3618 4503 5519 6676
100
27 4549 5740 7106 8660 10413
75.3 44.3
32 4313 5438 6726 8192 9847 2830 1.92 5539 2834 1.95 3.49
38 - 5067 6261 7621 9158
43 - 4747 5864 7135 8575
OP-MPPM035VVLP01E 114X4316 VLZ035TGA
30
27 1806 2259 2796 3426 4157
71.7 40.7
32 1692 2119 2626 3223 3916 1057 2.00
38 - 1956 2427 2983 3632
43 - - - - -
50
27 2988 3751 4643 5674 6854
72.3 41.3
32 2812 3542 4393 5378 6504 1599 2.22
38 - 3279 4079 5003 6061
43 - 3051 3803 4674 5674
75
27 4374 5503 6805 8291 9973
72.9 41.9
32 4128 5203 6439 7849 9443 2445 2.13
38 - 4824 5977 7292 8779
43 - 4492 5573 6806 8201
100
27 5666 7124 8782 10652 12744
74.6 43.6
32 5367 6741 8302 10064 12035 3488 1.93 6876 3494 1.97 3.63
38 - 6270 7715 9345 11172
43 - 5864 7212 8734 10442
OP-MPPM044VVLP01E 114X4334 VLZ044TGA
30
27 2303 2877 3556 4350 5268
72.6 41.6
32 2159 2699 3339 4091 4962 1278 2.11
38 - 2491 3085 3785 4600
43 - - - - -
50
27 3796 4757 5876 7163 8629
73.1 43.1
32 3569 4487 5553 6779 8175 1974 2.27
38 - 4148 5146 6294 7602
43 - 3852 4790 5870 7101
75
27 5527 6933 8542 10363 12405
73.7 43.7
32 5208 6543 8067 9790 11720 3073 2.13
38 - 6052 7468 9069 10862
43 - 5620 6944 8440 10117
100
27 7125 8914 10926 13170 15649
74.4 43.4
32 6738 8421 10311 12419 14750 4434 1.90 8612 4446 1.94 3.71
38 - 7813 9557 11502 13656
43 - 7288
8911 10721 12728
SEPR, Seasonal Energy Performance Ratio
Q [W], Cooling Capacity
P [W], Power Input
[1] Nominal conditions, Evaporating temperature -10°C. Ambient air temperature +32°C. Superheat 10K.
[2] Rated conditions, Evaporating temperature -10°C. Ambient air temperature +32°C. Return Gas Temperature 20°C
9FRCC.PC.044.A6.02
Application Guidelines

Table of Contents

Other manuals for Danfoss Optyma Plus