EcoDesign
For more information related to EcoDesign compliance, please refer to Coolselector®
coolselector.danfoss.com or contact Danfoss
Product description
2.8 Cooling capacities, sound data, power consumption
Optyma
™
Plus INVERTER, R407A
Model number
Code
number
Compressor
Compressor
speed, rps
Tamb [°C]
Cooling capacity Q [kW] P [kW] EcoDesign (2)
Sound power
level dB(A)
Sound pressure
level 10 m dB(A)
Te [°C]
COP
(1)
Q [kW] P [kW] COP
A
SEPR
-15 C -10 C -5 C 0 C 5 C -10°C
OP-MPPM028VVLP01E 114X4302 VLZ028TGA
30
27 1435 1797 2227 2732 3320
72.8 41.8
32 1345 1686 2092 2570 3128 899 1.88
38 - 1557 1934 2380 2902
43 - - - - -
50
27 2382 2994 3711 4543 5499
73.4 42.4
32 2243 2829 3515 4310 5224 1333 2.12
38 - 2622 3267 4015 4876
43 - 2442 3050 3757 4571
75
27 3499 4412 5470 6686 8069
74.0 43.0
32 3306 4177 5183 6339 7654 2005 2.08
38 - 3879 4821 5901 7131
43 - 3618 4503 5519 6676
100
27 4549 5740 7106 8660 10413
75.3 44.3
32 4313 5438 6726 8192 9847 2830 1.92 5539 2834 1.95 3.49
38 - 5067 6261 7621 9158
43 - 4747 5864 7135 8575
OP-MPPM035VVLP01E 114X4316 VLZ035TGA
30
27 1806 2259 2796 3426 4157
71.7 40.7
32 1692 2119 2626 3223 3916 1057 2.00
38 - 1956 2427 2983 3632
43 - - - - -
50
27 2988 3751 4643 5674 6854
72.3 41.3
32 2812 3542 4393 5378 6504 1599 2.22
38 - 3279 4079 5003 6061
43 - 3051 3803 4674 5674
75
27 4374 5503 6805 8291 9973
72.9 41.9
32 4128 5203 6439 7849 9443 2445 2.13
38 - 4824 5977 7292 8779
43 - 4492 5573 6806 8201
100
27 5666 7124 8782 10652 12744
74.6 43.6
32 5367 6741 8302 10064 12035 3488 1.93 6876 3494 1.97 3.63
38 - 6270 7715 9345 11172
43 - 5864 7212 8734 10442
OP-MPPM044VVLP01E 114X4334 VLZ044TGA
30
27 2303 2877 3556 4350 5268
72.6 41.6
32 2159 2699 3339 4091 4962 1278 2.11
38 - 2491 3085 3785 4600
43 - - - - -
50
27 3796 4757 5876 7163 8629
73.1 43.1
32 3569 4487 5553 6779 8175 1974 2.27
38 - 4148 5146 6294 7602
43 - 3852 4790 5870 7101
75
27 5527 6933 8542 10363 12405
73.7 43.7
32 5208 6543 8067 9790 11720 3073 2.13
38 - 6052 7468 9069 10862
43 - 5620 6944 8440 10117
100
27 7125 8914 10926 13170 15649
74.4 43.4
32 6738 8421 10311 12419 14750 4434 1.90 8612 4446 1.94 3.71
38 - 7813 9557 11502 13656
43 - 7288
8911 10721 12728
SEPR, Seasonal Energy Performance Ratio
Q [W], Cooling Capacity
P [W], Power Input
[1] Nominal conditions, Evaporating temperature -10°C. Ambient air temperature +32°C. Superheat 10K.
[2] Rated conditions, Evaporating temperature -10°C. Ambient air temperature +32°C. Return Gas Temperature 20°C
9FRCC.PC.044.A6.02
Application Guidelines