2
FRCC.EI.003.A1.02 © Danfoss Commercial Compressors 03/08
M
DGT
HP
180 s
TH
BP
CONTROL CIRCUIT
F1F1
KM
KM
KM
KA KA
A1
A2
A3
KA
KA
KS
KS
KS
L1 L3 L2
Q1
F2
T1
T3
T2
LLSV KS
SH 090 - 105 - 120 - 140 - 161
SM 084 - 090 - 100 - 110 - 120 - 124 - 147 - 148 - 161
SZ 084 - 090 - 100 - 110 - 120 - 148 - 161
SM 115 - 125 - 160 - 175 - 185
SZ 115 - 125 - 160 - 175 - 185
SH 240 - 300 - 380
SY 240 - 300 - 380
SZ 240 - 300 - 380
These Performer® compressors
are protected against overheating
and overloading by an internal
safety motor protector. However,
an external manual reset overload
protector is recommended for
protecting the circuit against over-
current.
These Performer® compressors
are provided with a bimetallic sin-
gle pole single throw thermostat
which is located in the motor win-
dings. Because the thermostat is
an automatic reset device, it must
be wired in a lockout safety circuit
with a manual reset to restart the
unit. For over-current protection,
an external manual reset overload
protector must be used.
The “must trip” value of these
overload relays must be set in ac-
cordance with power line sizing
and design and shall never exceed
the “A max.” value stamped on the
nameplate.
These Performer® compressors
motors are protected by an ex-
ternal module protecting against
phase loss/reversal, over heating
and high current draw.