Installation Instructions
GB
Wiring
Product overview
This thermostat is designed for fan coil and chilled beam
applications alongside proportional valves and actuator systems
where a 0-10v proportional control output is required.
The thermostat has a 3 speed fan output selectable via a switch on
the front of the unit.
The operational mode of the fan (auto or continuous is selected
at time of installation via DIL switches accessible on the rear of
the unit.
When the unit is in standby the fans are switched o .
Installation
First remove the wallplate from the back of the unit.
Fix at a height of approximately 1.5m from the  oor, away
from draughts or heat sources such a fan-coil outlets,
sunlight or o ce equipment.