EasyManua.ls Logo

Danfoss SONOMETER 1100 - Function Modules; Pulse Input Module; Pulse Output Module; Combined (IN;OUT) Module

Danfoss SONOMETER 1100
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instruction SONOMETER™ 1100
8.5 Pulse input function module
Module for two additional meters. Pulse input 1 is marked as “I1- ”,
input 2 with “I2 - . Pulse inputs can be programmed (IZAR@SET) with
a value: 1, 2.5, 10, 25, 100, 250, 1000, 2500 litre per pulse.
Pulse transmitter must be electrically isolated, e.g. Reed contact
Possible units are all the energy units available in the meter, the
volume unit m³ or no unit.
Data is accumulated separately in registers; can be read in the dis-
play as IN1 and IN2 and can be transferred via the communication
modules.
8.6 Pulse output function module
The module is equipped with 2 pulse outputs, which can be freely
programmed using the IZAR@SET software. The outputs are marked
as “O1 - “ and “O2 - “ on the terminal strip and as Out1 and Out2
on the display.
External supply: Vcc = 3-30 VDC
Output current ≤ 20 mA with a residual voltage of ≤ 0.5 V
Open Collector (Drain)
Electrically isolated
Output 1: f ≤ 4 Hz Pulse duration: 125 ms ±10 %
Pulse pause: ≥ 125 ms –10 %
Output 2: f ≤ 100 Hz Pulse duration pulse/pause ~1:1
The volume pulse rate can be freely programmed
Standard: last digit in the display
8.7 Combined function module (IN/OUT)
The combined module has 2 inputs and 1 output.
See chapter 8.5 for the specic characteristics on the pulse input.
A 3 VDC voltage is connected to the “+” terminal and can be used as
the supply for a ow sensor.
The pulse output has the same characteristics as pulse output 1 speci-
ed under 8.6. It is not, however, electrically isolated.
8.8 Analogue output function module
The module has 2 passive analogue output connections which are
freely programmable using the IZAR@SET software. On the terminal
strip, the electrically isolated outputs “1” and “2” are marked and the
polarity is indicated (“+” and “–”).
Passive, external power supply: 10…30 VDC
Current loop 4 … 20 mA whereat 4 mA = 0 value;
20 mA = programmable maximum value
Overload up to 20.5 mA, then residual current
The module displays errors with 3.5 mA or 22.6 mA
(programmable)
Output values: power, ow, temperatures
8.9 Test output
The internally located test output is intended for testing
laboratories. The manufacturer supplies two special cables:
1. Volume testing pulse
2. Energy testing pulse
Please refer to the inspection and testing manual for further
specications (pulse rate, pulse duration/pause, pulse frequency).
Input frequency ≤ 8 Hz
Min. pulse duration 10 ms
Input resistance 2.2 M
Terminal voltage 3 VDC
Cable length up to 10 m
The module is connected with the meter electronics by means of
a ribbon cable. The separate plug connector on module slot 2 is
necessary for the perfect functioning of the analogue outputs.
Ensure that the temperature sensors (measurement resistances)
remain in contact without interruption during energy verication.
T
T
T T
Danfoss District Energy VI.SH.K1.02 DEN-SMT/PL
7

Related product manuals