InstallationGuideTermixVVX-I
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall
radiatorscomparedtothetotalheating
requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface.
Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly
acrossthefullheatingsurface–openall
radiatorsandkeeptheradiatorsinthe
systemfromheatingupatthebottom.It
isextremelyimportanttokeepthesupply
temperaturetotheradiatorsaslowas
possible,whilemaintainingareasonable
levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic
controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator
valve(s).Singlepipeloopsystemsrequire
specialone-piperadiatorvalves.
Check–set/replace.
Dirtinthemotorizedvalveorinthe
differentialpressurecontroller.
Check–cleanout.
Defectivemotorizedvalve,sensoror
automaticcontroller.
Check–replace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror
electroniccontroller.
Check–replace.