VLT
®
6000 HVAC Series
[0]. In Closed loop [1] (parameter 100), Ref
HIGH
must be within the reference range programmed
in parameters 204 and 205.
227 Warning: Low feedback, FB
LOW
(WARN LOW FDBK)
Value:
-999,999.999 - FB
HIGH
(parameter 228)
-999.999,999
Function:
If the feedback signal is below the limit, FB
LOW
,
programmed in this parameter, the display will
show a flashing FEEDBACK LOW.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while
stopped. The warning functions are activated when
the output frequency has reached the selected
reference. The signal outputs can be programmed
to generate a warning signal via terminal 42 or
45 and via the relay outputs.
In Closed loop, the unit for the feedback is programmed
in parameter 415 Process units.
Description of choice:
Set the required value within the feedback range
(parameter 413 Minimum feedback, FB
MIN
,and
414 Maximum feedback, FB
MAX
).
228 Warning: High feedback, FB
HIGH
(WARN. HIGH FDBK)
Value:
FB
LOW
(parameter 227) - 999,999.999
999.999,999
Function:
If the feedback signal is above the limit, FB
HIGH
,
programmed in this parameter, the display will
show a flashing FEEDBACK HIGH.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while stopped.
The warning functions are activated when the output
frequency has reached the selected reference.
The signal outputs can be programmed to
generate a warning signal via terminal 42 or
45 and via the relay outputs.
In Closed loop, the unit for the feedback is programmed
in parameter 415 Process units.
Description of choice:
Set the required value within the feedback range
(parameter 413 Minimum feedback, FB
MIN
,and
414 Maximum feedback, FB
MAX
).
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
100

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals