VLT
®
6000 HVAC Series
Load and Motor 100-117
This parameter group allows
the con-figuration of regulation
parameters and the choice of
torque characteristics to which
the frequency converter is to be
adapted.
Themotornameplatedatamust
be
set and automatic motor adaptation can be carried
out. In addition, DC brake parameters can be set
and the motor thermal protection can be activated.
Configuration
The selection of configurati
on and torque characteristics
influences the parameters that can be seen in the
display. If Open loop [0] is selected, all parameters
relating to PID regul
ation will be hidden.
Consequently, the user is only able to see
the parameters that are of significance for
a given applicatio
n.
100 Configurati
on
(CONFIG. MODE)
Value:
Open loop (OPEN LOOP)
[0]
Closed loop (CLOSED LOOP)
[1]
Function:
This parameter is used for selecting the configuration
to which the frequency converter is to be adapted.
Description of choice:
If Open loop [0] is selected, normal speed control is
obtained (withou
t feedback signal), i.e. if the reference
is changed, the motor speed will change.
If Closed loop [1] is selected, the internal process
regulator is ac
tivated to enable accurate regulation
in relation to a given process signal.
The reference (setpoint) and the process signal
(feedback) ca
n be set to a process unit as
programmed in parameter 415 Process units.
See Feedback handling.
101 Torque characteristics
(VT CHARACT)
Value:
Automatic Energy Optimisation
(AEO FUNCTION)
[0]
Parallel motors (MULTIPLE MOTORS)
[1]
Function:
This parameter allows a choice of whether the frequency
converter has one or several motors connected to it.
Description of choice:
If Automatic Energy Optimisation [0] has been selected,
only one motor may be connected to the frequency
converter. The AEO function ensures that the motor
obtains its maximum efficiency and minimises motor
interference. Parameter 118 makes it possible to set the
powerfactor(Cosϕ) which is used by the AEO function.
Select Parallel motors [1] if more than one motor is
connected to the output in parallel. See the description
under parameter 108 Start voltage of parallel motors
regarding the setting of parallel motor start voltages.
102 Motor power, P
M,N
(MOTOR POWER)
Value:
0.25 kW (0.25 KW)
[25]
0.37 kW (0.37 KW)
[37]
0.55 kW (0.55 KW)
[55]
0.75 kW (0.75 KW)
[75]
1.1 kW (1.10 KW)
[110]
1.5 kW (1.50 KW)
[150]
2.2 kW (2.20 KW)
[220]
3 kW (3.00 KW)
[300]
4 kW (4.00 KW)
[400]
5,5 kW (5.50 KW)
[550]
7,5 kW (7.50 KW)
[750]
11 kW (11.00 KW)
[1100]
15 kW (15.00 KW)
[1500]
18.5 kW (18.50 KW)
[1850]
22 kW (22.00 KW)
[2200]
30 kW] (30.00 KW)
[3000]
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
86

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals