VLT
®
6000 HVAC Series
0-f
MAX
0-20 mA and
0-f
MAX
4-20 mA and
0-f
MAX
0-32000 p which generates an output signal
proportional to the output frequency in the interval 0 -
f
MAX
(parameter 202 Output frequency, high limit, f
MAX
).
External Ref
min
-Ref
max
0-20 mA and
External Ref
min
-Ref
max
4-20 mA and
External Ref
min
-Ref
max
0-32000 p which
generates an output signal proportional to the resulting
reference value in the interval Minimum reference, Ref
MIN
- Maximum reference, Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
0-20 mA and
FB
MIN
-FB
MAX
4-20 mA and
FB
MIN
-FB
MAX
0-32000 p, an output signal
proportional to the reference value in the interval
Minimum feedback, FB
MIN
- Maximum feedback,
FB
MAX
(parameters 413/414) is obtained.
0-I
VLT, MAX
0-20 mA and
0-I
VLT, MAX
4-20 mA and
0-I
VLT, MAX
0-32000 p, an output signal
proportional to the output current in the interval
0-I
VLT,MAX
is obtained.
0-P
NOM
0-20 mA and
0-P
NOM
4-20 mA and
0-P
NOM
0-32000p, which generates an
output signal proportional to the present output
power. 20 mA corresponds to the value set in
parameter 102 Motor power, P
M,N
.
0.0 - 100.0%
0-20mAand
0.0 - 100.0%
4-20mAand
0.0 - 100.0%
0 - 32.000 pulses which generates an
output signal proportional to the value (0.0-100.0%)
received by serial communication. Writing from Serial
communication is done to parameter 364 (terminal
42) and 365 (terminal 45). This function is limited to
the following protocols: FC bus, Profibus, LonWorks
FTP, DeviceNet, Metasys N2 and Modbus RTU.
Fire Mode active is indicated on the output when
activated via input 16 or 17.
Fire Mode bypass is indicated on the output
when Fire Mode has been active and a certain trip
occurred (please see description of Fire Mode). A
delay for this indication can be programmed in
parameter 432. Please select Fire Mode bypass in
parameter 430 to enable this function.
320 Terminal 42, output, pulse scaling
(AO 42 PULS SCALE)
Value:
1 - 32000 Hz
5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value.
321 Terminal 45, output
(AO 45 FUNCTION)
Value:
See description of parameter 319 Terminal 42, Output.
Function:
This output can function both as a digital or an analog
output. When used as a digital output (data value
[0]-[26]) it generates a 24 V (max. 40 mA) signal. For
the analog outputs (data value [27] - [41]) there is a
choice of 0-20 mA, 4-20 mA or a pulse sequence.
Description of choice:
See description of parameter 319 Terminal 42, Output.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
110

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals