VLT
®
6000 HVAC Series
Programming
Description of choice:
Set the required time delay before trip and
setting the output.
483 Dynamic DC link compensation
(DC LINK COMP.)
Value:
Off
[0]
On
[1]
Function:
The frequency converter includes a feature, which
ensures that the output voltage is independent of
any voltage fluctuation in the DC link, e.g. caused
by fast fluctuation in the mains supply voltage. The
benefit is a very steady torque on motor shaft (low
torque ripple) under most mains conditions.
Description of choice:
In some cases this dynamic compensation can
cause resonances in the DC link and should then
be disabled. Typical cases are where a line choke or
a passive harmonic filter (e.g. filters AHF005/010)
is mounted in the mains supply to the frequency
converter to suppress harmonics. Can also occur
on mains with low short circuit ratio.
500 - 566 Serial communication
Value:
All information concerning the use of RS 485 serial
interface is not included in this manual. Please contact
Danfoss and ask for the VLT 6000 HVAC Design Guide.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
129

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals