EasyManua.ls Logo

Danfoss VLT 6000 series - Page 158

Danfoss VLT 6000 series
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VLT
®
6000 HVAC Series
Immunity, continued
VLT 6002-6550 380-460 V, VLT 6002-6027 200-240 V
Burst Surge ESD Radiated electro- Mains RF common Radiated radio
Basic standard IEC 1000-4-4 IEC 1000-4-5 1000-4-2 magnetic field distortion mode voltage freq.elect.field
IEC 1000-4-3 VDE 0160 ENV 50141 ENV 50140
Acceptance criterion B B B A A A
Port connection CM DM CM - - CM CM
Line OK OK - - - OK OK -
Motor OK --- - - OK -
Control lines OK -OK- - - OK -
PROFIBUS option OK -OK- - - OK -
Signal Interface<3 m OK --- - - - -
Enclosure - --OK OK - - OK
Load sharing OK --- - - OK -
Standard bus OK -OK- - - OK -
Basic specifications - - - -
Line 4kV/5kHz/DCN 2kV/2 4kV/12 - - 2,3 x U
N
2)
10 V
RMS
-
Motor 4kV/5kHz/CCC --- - - 10 V
RMS
-
Control lines 2kV/5kHz/CCC -2kV/2
1)
- - - 10 V
RMS
-
PROFIBUS option 2kV/5kHz/CCC -2kV/2
1)
- - - 10 V
RMS
-
Signal interface<3 m 1kV/5kHz/CCC --- - - 10 V
RMS
-
Enclosure - --8kVAD
6kVCD
10 V/m
- - -
Load sharing 4kV/5kHz/CCC --- - - 10 V
RMS
-
Standard bus 2kV/5kHz/CCC -4kV/2
1)
- - - 10 V
RMS
-
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
1
) Injection on cable shield
2
)2.3xU
N
:max.testpulse380V
AC
: Class 2/1250 V
PEAK
, 415 VAC: Class 1/1350 V
PEAK
MG.61.A5.02 - VLT is a registered Danfoss trademark