VLT
®
6000 HVAC Series
Technical data, mains supply 3x380-460V
According to international requirements VLT type 6052 6062 6072 6102 6122
Output current I
VLT,N
[A] (380-440 V) 73.0 90.0 106 147 177
I
VLT, MAX
(60 s) [A]
(380-440 V)
80.3 99.0 117 162 195
I
VLT,N
[A] (441-460 V) 65.0 77.0 106 130 160
I
VLT, MAX
(60 s) [A]
(441-460 V)
71.5 84.7 117 143 176
Output power S
VLT,N
[kVA] (400 V) 52.5 64.7 73.4 102 123
S
VLT,N
[kVA] (460 V) 51.8 61.3 84.5 104 127
Typica l sh af t ou tput P
VLT,N
[kW] 37 45 55 75 90
Typica l sh af t ou tput P
VLT,N
[HP] 50 60 75 100 125
Max. cable
cross-section to motor
and DC-bus, IP 20
35/2 50/0 50/0
120 /
250
mcm
5)
120 /
250
mcm
5)
Max. cable
cross-section to motor
and DC-bus, IP 54
[mm
2
]/[AWG]
2) 4) 6)
35/2 50/0 50/0
150 /
300
mcm
5)
150 /
300
mcm
5)
Min. cable cross-section
to motor and DC-bus
[mm
2
]/[AWG]
2) 4)
10/8 16/6 16/6 25/4 25/4
Max. input current I
L,N
[A] (380 V) 72.0 89.0 104 145 174
(RMS) I
L,N
[A] (460 V) 64.0 77.0 104 128 158
Max. cable
cross-section power,
IP 20
35/2 50/0 50/0
120 /
250
mcm
120 /
250
mcm
Max. cable
cross-section power,
IP 54
[mm
2
]/[AWG]
2) 4) 6)
35/2 50/0 50/0
150 /
300
mcm
150 /
300
mcm
Max. pre-fuses [-]/UL
1)
[A] 100/100 125/125 150/150 225/225 250/250
Efficiency at rated frequency 0.96 0.96 0.96 0.98 0.98
Weight IP 20 [kg] 41 42 43 54 54
Weight IP 54 [kg] 56 56 60 77 77
Power loss at max. load. [W] 1275 1571 1322 1467 1766
Enclosure IP 20/IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be
fitted on the terminals. Max. cable cross section is the maximum possible
cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
5. DC connection 95 mm
2
/AWG 3/0.
6. Aluminium cables with cross-section above 35 mm
2
must be con-
nected by use of an Al-Cu connector.
MG.61.A5.02 - VLT is a registered Danfoss trademark