VLT
®
6000 HVAC Series
NonULcompliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 6002-6032 200-240 V type gG
VLT 6042-6062 200-240 V type gR
VLT 6002-6072 380-460 V type gG
VLT 6102-6122 380-460 V type gR
VLT 6152-6352 380-460 V type gG
VLT 6402-6602 380-460 V type gR
VLT 6002-6072 525-600 V type gG
Not following the recommendation may result in damage of the drive in case of malfunction. Fuses must
be designed for protection in a circuit capable of supplying a maximum of 100000 A
rms
(symmetrical),
500 V / 600 V maximum.