VLT
®
8000 AQUA
Installation
Technical data, mains supply 3 x 525 - 600 V
According to international requirements VLT type 8002 8003 8004 8005 8006 8008 8011
Output current I
VLT,N
[A] (550 V) 2.6 2.9 4.1 5.2 6.4 9.5 11.5
I
VLT, MAX
(60 s) [A] (550 V) 2.9 3.2 4.5 5.7 7.0 10.5 12.7
I
VLT,N
[A] (575 V) 2.4 2.7 3.9 4.9 6.1 9.0 11.0
I
VLT, MAX
(60 s) [A] (575 V) 2.6 3.0 4.3 5.4 6.7 9.9 12.1
Output S
VLT,N
[kVA] (550 V) 2.5 2.8 3.9 5.0 6.1 9.0 11.0
S
VLT,N
[kVA] (575 V) 2.4 2.7 3.9 4.9 6.1 9.0 11.0
Typical shaft output P
VLT,N
[kW] 1.1 1.5 2.2 3 4 5.5 7.5
Typical shaft output P
VLT,N
[HP] 1.5 2 3 4 5 7.5 10
Max. copper cable cross-section to motor and
loadsharing
[mm
2
]4 4444 44
[AWG]
2)
10 10 10 10 10 10 10
Rated Input
Current
I
VLT,N
[A] (550 V)
I
VLT,N
[A] (600 V)
2.5
2.2
2.8
2.5
4.0
3.6
5.1
4.6
6.2
5.7
9.2
8.4
11.2
10.3
Max.copper cable cross-section, power
[mm
2
]4 4444 44
[AWG]
2)
10 10 10 10 10 10 10
Max. prefuses (mains)
1)
[ - ]/UL [A] 3 4 5 6 8 10 15
Efficiency 0.96
Weight IP 20
/NEMA1
[kg/lbs]
10.5/
23
10.5/
23
10.5/
23
10.5/
23
10.5/
23
10.5/
23
10.5/
23
Estimated power loss at max. load (550 V) [W] 65 73 103 131 161 238 288
Estimated power loss at max. load (600V) [W] 63 71 102 129 160 236 288
Enclosure IP 20/NEMA 1
1. For type of fuse, see section Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply
with IP20. Always comply with national and local regulations on min. cable cross-section.