VLT
®
8000 AQUA
Installation
■ Technical data, mains supply 3 x 525 - 690 V
According to international requirements VLT type 8502 8602 8652
Output current I
VLT,N
[A] (525-550 V) 523 596 630
I
VLT, MAX
(60 s) [A] (525-550 V) 575 656 693
I
VLT,N
[A] (551-690 V) 500 570 630
I
VLT, MAX
(60 s) [A] (551-690 V) 550 627 693
Output power S
VLT,N
[kVA] (550 V) 498 568 600
S
VLT,N
[kVA] (575 V) 498 568 627
S
VLT,N
[kVA] (690 V) 598 681 753
Typical shaft output (525-550 V) P
VLT,N
[kW] 500 560 630
Typical shaft output (551-690 V) P
VLT,N
[HP] 400 500 600
Max. cable cross-section to motor and DC-bus [mm
2
]
4) 5)
4 x 240 4 x 240 4 x 240
Max. cable cross-section to motor and DC-bus [AWG]
2)
4) 5)
4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
I
L,MAX
[A] (550 V) 504 574 607
I
L,MAX
[A] (575 V) 482 549 607
Max. input
current (RMS)
I
L,MAX
[A] (690 V) 482 549 607
Max. cable cross-section to power [mm
2
]
4) 5)
4 x 240 4 x 240 4 x 240
Max. cable cross-section to power [AWG]
2) 4) 5)
4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. pre-fuses
(mains) [-]/UL [A]
1)
700/700 900/900 900/900
Efficiency
3)
0.98 0.98 0.98
Weight IP 00/
Chassis [kg/lbs] 221/488 236/520 277/611
Weight IP 20/
NEMA 1 [kg/lbs] 263/580 272/600 313/690
Weight IP 54/
NEMA 12 [kg/lbs] 263/580 272/600 313/690
Power loss at
max. load [W] 7249 8727 9673
Enclosure IP 00/Chassis/IP 21/NEMA 1/IP 54/NEMA 12
1.Fortypeoffuse,seesectionFuses.
2. American Wire Gauge.
3. Measured using 30 m/100 ft screened motor cables at rated load and rated frequency.
4. Always comply with national and local regulations on min. cable cross-section. Max. cable cross section
is the maximum possible cable cross section that can be fitted on the terminals.
5. Connection bolt, power supply, motor and load sharing: M10 (compression lug), 2 x M8 (box lug)
MG.83.A2.02 - VLT is a registered Danfoss trademark
47